Under Cal/OSHA, the height that triggers fall protection depends on the work. General construction at an edge or opening needs it for a fall of more than 7 1/2 feet (8 CCR §1670). Residential-type framing and residential-type roofing up to 7:12 need it at 6 feet or more, a change that took effect July 1, 2025 (8 CCR §1716.2, 8 CCR §1731). Non-residential roofing needs it on roofs more than 20 feet high (8 CCR §1730). A guardrail's top rail is 42 to 45 inches high (8 CCR §1620), a ladder extends 36 inches above the landing (8 CCR §3276), and a scaffold carries 4 times its intended load (8 CCR §1637).
CSLB's B study guide lists personnel safety as one of the three Safety subtopics. This guide covers the fall protection table, personal fall arrest, roofing, guardrails and openings, stairways, ladders and scaffolds, with a worked example wherever a question would need arithmetic. Every rule comes from Title 8 of the California Code of Regulations, which is free to read online. Older books show older heights, so check the date on anything you study from.
Which height applies
Read the kind of work first, then pick the height. This is the most tested table in the Safety section.
| Work | Fall protection required | Source |
|---|---|---|
| General construction: perimeters, edges, leading edges, shafts, openings | Fall of more than 7 1/2 feet | 8 CCR §1670 |
| General work on roofs steeper than 7:12, or surfaces steeper than 40 degrees | Fall of more than 7 1/2 feet | 8 CCR §1670 |
| Residential-type framing (houses and light commercial) | 6 feet or more | 8 CCR §1716.2 |
| Residential-type roofing, 0:12 through 7:12 | 6 feet or more | 8 CCR §1731 |
| Residential-type roofing steeper than 7:12 | Any height | 8 CCR §1731 |
| Non-residential roofing | Roofs more than 20 feet high | 8 CCR §1730 |
| Walking trusses, beams, purlins or plates 4 inches nominal or wider, guardrails impracticable | More than 15 feet | 8 CCR §1669 |
| Safety nets where other systems are clearly impractical | 25 feet or more | 8 CCR §1671 |
Example: A crew reroofs a one-story house with a 4:12 roof. The eave is 10 feet above the ground. That is residential-type roofing at 4:12, and 10 feet is more than 6 feet, so fall protection is required. On the same house with a 9:12 roof, it would be required at any height.
Example: An HVAC crew installs ductwork near the open edge of a mezzanine in a commercial building. That is neither roofing nor residential-type framing, so the general rule applies: more than 7 1/2 feet.
Personal fall arrest and positioning
- Free fall. Rig a personal fall arrest system so the worker cannot free fall more than 6 feet or hit a lower level. (8 CCR §1670)
- Harness, not belt. With a body harness, the system limits the arresting force to 1,800 pounds and the deceleration distance to 3.5 feet. Body belts may not be used for fall arrest. (8 CCR §1670)
- Anchorage. At least 5,000 pounds per attached worker, unless it is part of a complete system designed with a safety factor of at least two under the supervision of a qualified person. Lanyards and vertical lifelines have a breaking strength of at least 5,000 pounds. Do not tie off to a guardrail. Each worker on a vertical lifeline has a separate lifeline. (8 CCR §1670)
- Inspection. Check the system before each use, and have a competent person inspect each system at least twice a year, with the dates documented. (8 CCR §1670)
- After a fall. Any part that has arrested a fall is removed from service at once and not used again. The employer also provides for prompt rescue. (8 CCR §1670)
- Positioning devices limit free fall to 2 feet, with an anchorage that holds twice the intended load or 3,000 pounds, whichever is greater. A fall restraint anchorage holds 4 times the intended load. (8 CCR §1670)
Nets, plans and controlled access zones
- Safety nets hang no more than 10 feet below the work. They extend outward 8 feet when up to 5 feet below the work, 10 feet when 5 to 10 feet below, and 13 feet when 10 to 30 feet below. (8 CCR §1671)
- Fall protection plans may replace guardrails, nets or personal fall protection only when the employer shows that conventional protection is infeasible or creates a greater hazard. A qualified person prepares the plan for that specific site; it is kept at the site and carried out under a competent person. (8 CCR §1671.1)
- Controlled access zones. The control line goes 6 to 25 feet from the unprotected or leading edge (precast concrete erection has its own limit), is flagged every 6 feet or less, hangs 39 to 45 inches above the working level and has a breaking strength of at least 200 pounds. A safety monitor is a competent person within sight of the workers and able to talk with them. (8 CCR §1671.2)
Residential-type framing
- The 6-foot rule. Workers on top plates, joists, rafters, trusses and beams, on floors that will later be enclosed by framed walls, and installing starter board, roof sheathing and fascia are protected at 6 feet or more, by scaffolding, guardrails, safety nets or personal fall protection. (8 CCR §1716.2)
- Tall walls raised by hand. Before a wall 15 feet or more tall is raised by hand, install temporary restraints, such as cleats on the floor or straps on the bottom plate, so the plate cannot slide or lift. Anchor bolts alone do not count. (8 CCR §1716.2)
- Edge protection scaffold. A scaffold used as an edge protection platform is fully planked, no more than 2 feet below the top plate and no more than 16 inches from the wall. (8 CCR §1716.2)
- Bracing first. Do not walk or work on plates, joists, rafters or trusses until they are braced and supported. (8 CCR §1716.2)
Roofing
- Residential-type roofing is protected at 6 feet or more on slopes of 0:12 through 7:12, and at any height on slopes steeper than 7:12. (8 CCR §1731)
- Non-residential roofing is protected on roofs more than 20 feet high. On a single-unit (monolithic) covering sloped 0:12 to 4:12, such as a built-up roof, a warning line goes no closer than 5 feet to the edge. Where felt-laying machines or ride-on equipment are used, the protection applies at any roof height, and the headers go at least 10 feet back from the edges the equipment moves toward (where headers cannot be used, the warning line goes 10 feet back there). (8 CCR §1730)
- Multiple-unit coverings, such as tile on slopes over 5:12, may be protected by a parapet at least 24 inches high, personal fall protection, catch platforms, scaffold platforms, eave barriers or roof jacks. (8 CCR §1730)
Guardrails and openings
- Where required. Guardrails go on all open sides and ends of scaffolds, runways, ramps, platforms and other elevations 7 1/2 feet or more above the ground or floor. (8 CCR §1621)
- Rail heights. The top rail is 42 to 45 inches above the walking surface, with a mid-rail halfway between. No mid-rail is needed where a wall or parapet is at least 21 inches high. (8 CCR §1620)
- Strength. The top rail resists 200 pounds in any outward or downward direction and may not deflect below 39 inches under that load. The mid-rail resists 150 pounds. (8 CCR §1620)
- Wood rails. Posts at least 2x4, no more than 8 feet apart; a 2x4 or larger top rail; a mid-rail at least 1x6. Steel or plastic banding may not be used as a rail. (8 CCR §1620)
- Toeboards are at least 4 inches (nominal) high with no more than 1/4 inch of clearance above the floor. (8 CCR §1621)
- Floor and roof opening covers support the greater of 400 pounds or twice the weight that may be on any one square foot, are secured against shifting, and are marked "Opening--Do Not Remove" in letters at least 1 inch high. (8 CCR §1632)
- Wall openings are guarded when the drop is more than 4 feet and the bottom of the opening is less than 3 feet above the working surface. (8 CCR §1632)
Example: A window opening has its sill 18 inches above the floor and a 14-foot drop outside. The drop is more than 4 feet and the sill is under 3 feet, so the opening must be guarded.
Stairways on the job
- A stairway, ramp or ladder is required at any break in elevation of 18 inches or more in a frequently used passageway, entry or exit. (8 CCR §1629)
- A building 2 or more stories, or 24 feet or more in height or depth, needs stairways. One is enough up to 3 stories or 36 feet; above that, provide 2 or more. (8 CCR §1629)
- In a wood frame building, the stairway to the second or higher floor is finished before the studs are raised for the next floor. (8 CCR §1629)
- Stair rails are 34 to 38 inches above the tread, measured at the riser face. A temporary handrail has at least 3 inches of clearance from the wall. (8 CCR §1626)
Ladders
Where no stairway or ramp is provided, ladders give access to every level. Construction ladders follow the General Industry ladder section, and single-rail ladders may not be used. (8 CCR §1675)
- Above the landing. Side rails extend at least 36 inches above the upper landing. If that is not possible, secure the top to a rigid support and provide a grab device. (8 CCR §3276)
- Pitch. Set the foot out one-quarter of the working length from the top support. (8 CCR §3276)
- Top rungs. Do not stand and work on the top 3 rungs of a single or extension ladder unless the structure gives a firm handhold or the worker has personal fall protection. (8 CCR §3276)
- Stepladders. Do not sit, kneel or stand on the top cap, the pail shelf, or the step below the top cap (unless that step is 18 inches below the top cap). Do not use a stepladder as a single ladder or partly closed. (8 CCR §3276)
- Damage. Take a defective ladder out of service and tag it "Dangerous, Do Not Use" until it is repaired or destroyed. (8 CCR §3276)
- Extension overlap. 36 inches up to 32 feet; 46 inches over 32 to 36 feet; 58 inches over 36 to 48 feet; 70 inches over 48 to 60 feet. (8 CCR §3276)
- Job-built ladders. A double cleat ladder is used where it is the main access for 25 or more workers or two-way traffic is expected; it may be no longer than 24 feet. A single cleat ladder may be no longer than 30 feet. (8 CCR §1629)
Example: An extension ladder has a working length of 20 feet. 20 ÷ 4 = 5 feet from the wall to the foot. A 34-foot two-section extension ladder needs a 46-inch overlap.
Scaffolds
- Capacity. A scaffold supports its own weight plus 4 times its maximum intended working load. Light, medium and heavy duty are 25, 50 and 75 pounds per square foot. (8 CCR §1637)
- Planks. Solid sawn planks are at least 2x10 scaffold grade. For 2x10 Douglas fir or southern pine the span is 10 feet at 25 psf, 8 feet at 50 psf and 7 feet at 75 psf. A plank overhangs its support no more than 18 inches unless access to the overhang is blocked or the other end is anchored. (8 CCR §1637)
- Supervision. A qualified person supervises and directs erection and dismantling. (8 CCR §1637)
- Rolling and tower scaffolds that are not guyed or tied keep the least base dimension at least one-third of the height, and the wheels are locked while the scaffold is in use. (8 CCR §1646)
- Horse scaffolds are no more than 10 feet or 2 tiers high (8 CCR §1647); ladder-jack platforms no more than 16 feet (8 CCR §1648).
Example: A rolling scaffold has a 5-by-7-foot base and is not tied. The least base dimension is 5 feet, so the scaffold may be no taller than 5 × 3 = 15 feet.
Traps to watch for
- Old heights. The 6-foot residential framing and roofing rules date from July 1, 2025. A book that shows other numbers is out of date.
- "More than" or "or more." Personal fall protection in general construction is for a fall of more than 7 1/2 feet (section 1670), while guardrails on platforms start at 7 1/2 feet or more (section 1621) and residential framing and roofing at 6 feet or more. Read the exact words.
- 6 feet means two things. It is the residential trigger height and also the most a worker may free fall in an arrest system.
- Roof type decides the roofing rule. A house roof is residential-type roofing; a commercial built-up roof uses the 20-foot rule.
- Overlap grows with length. Find the ladder length band before you answer.
How to use this guide
Memorize the height table and the guardrail numbers first, then work the ladder and scaffold examples by hand. Then answer the practice questions below this guide. The rest of the Safety section, from toilets and fire extinguishers to traffic control, is in our B exam safety notes, and more answered questions are on the personnel safety practice page.