GFCI, AFCI and Outlet Rules for California Homes (2025 CEC)

Section 3 of 5, about 30% of the B exam

Updated

California's electrical code is the 2025 California Electrical Code (CEC), which is the 2023 NEC with California amendments and the NEC's section numbers. In a home, GFCI protection is required for receptacles in bathrooms, kitchens, garages, outdoors, laundry areas, basements and the other places on the list in 2025 CEC §210.8, including 120/240-volt receptacles. AFCI protection covers 120-volt, 10-, 15- and 20-amp circuits in kitchens, bedrooms, living areas, hallways, closets and laundry areas, but not bathrooms or garages (2025 CEC §210.12). Wall receptacles are placed so no point along the floor line is more than 6 feet from one, and kitchen countertop receptacles so no point along the wall line is more than 24 inches from one (2025 CEC §210.52).

This guide covers the dwelling rules that trade questions are built on: GFCI and AFCI, required branch circuits, where receptacles go, protecting cable in framing, burial depth, and the two different GFCI rules for temporary power on a job site. The CEC is Part 3 of Title 24, listed in CSLB's B study guide as a reference. NFPA lets you read the 2023 NEC free online, and its section numbers are the ones cited here.

GFCI protection in homes

Where GFCI is required

In a dwelling, GFCI protection is required for all 125-volt through 250-volt receptacles on single-phase branch circuits of 150 volts or less to ground in these places (2025 CEC §210.8):

  • bathrooms and kitchens;
  • areas with a sink and permanent provisions for food or beverage preparation or cooking;
  • within 6 feet of the top inside edge of a sink bowl;
  • within 6 feet of the outside edge of a bathtub or shower stall;
  • garages, and accessory buildings with a floor at or below grade that are not habitable rooms;
  • outdoors;
  • crawl spaces at or below grade, and basements;
  • laundry areas and boathouses; and
  • indoor damp and wet locations.

The 6 feet is measured the shortest way a cord could run, without passing through a floor, wall, ceiling, fixed barrier or door. The GFCI device must be readily accessible. (2025 CEC §210.8)

Because the list covers receptacles up to 250 volts, the 120/240-volt dryer receptacle in a laundry area needs GFCI protection, along with the washer receptacle. So does a 120/240-volt range receptacle in a kitchen. (2025 CEC §210.8)

Appliances and outdoor outlets

  • Some appliances need GFCI protection when rated 150 volts or less to ground and 60 amps or less. In homes these include dishwashers, electric ranges, wall-mounted ovens, counter-mounted cooking units, clothes dryers, microwave ovens and sump pumps. (2025 CEC §210.8)
  • Outdoor outlets at a dwelling on single-phase circuits of 150 volts or less to ground and 50 amps or less need GFCI protection. Outdoor lighting outlets are excepted. (2025 CEC §210.8)
  • The receptacle required within 25 feet of heating, air-conditioning and refrigeration equipment, on the same level (2025 CEC §210.63), needs GFCI protection too (2025 CEC §210.8).

AFCI protection in homes

An AFCI cuts power when it detects a dangerous arc, which can start a fire. In a dwelling, every 120-volt, single-phase, 10-, 15- and 20-amp branch circuit supplying outlets or devices in these rooms needs AFCI protection: kitchens, family rooms, dining rooms, living rooms, parlors, libraries, dens, bedrooms, sunrooms, recreation rooms, closets, hallways, laundry areas and similar areas. (2025 CEC §210.12)

  • Not on the list: bathrooms, garages and outdoor areas. (2025 CEC §210.12)
  • Usual method: a listed combination-type AFCI breaker at the start of the circuit, which protects the whole circuit. An outlet-type AFCI at the first outlet is allowed with a listed breaker if the run to that first outlet is no longer than 50 feet of 14 AWG or 70 feet of 12 AWG wire, and the first box is marked. (2025 CEC §210.12)
  • Remodels. When wiring in those rooms is changed, replaced or extended, the circuit gets AFCI protection, at the breaker or at the first receptacle of the existing circuit. No AFCI is needed for an extension of 6 feet or less that adds no outlets or devices. (2025 CEC §210.12)
Location GFCI receptacles AFCI circuits Source
Kitchen Yes Yes 2025 CEC §§210.8, 210.12
Laundry area Yes Yes 2025 CEC §§210.8, 210.12
Bathroom Yes No 2025 CEC §§210.8, 210.12
Garage Yes No 2025 CEC §§210.8, 210.12
Outdoors Yes No 2025 CEC §§210.8, 210.12
Bedroom, living room, hallway, closet No (unless near a sink, or damp or wet) Yes 2025 CEC §§210.8, 210.12

Required branch circuits

Besides its other circuits, every dwelling unit needs (2025 CEC §210.11(C)):

  • two or more 20-amp small-appliance circuits for the kitchen, pantry, breakfast room, dining room and similar areas, with the countertop receptacles fed by at least two of them;
  • at least one 20-amp laundry circuit, with no other outlets;
  • one or more 120-volt, 20-amp bathroom circuits, with no other outlets. One circuit may feed the receptacles of several bathrooms; a 20-amp circuit that serves only one bathroom may also feed other equipment in that bathroom; and
  • at least one 120-volt, 20-amp garage circuit for an attached garage, or a detached garage with power, which may also feed outdoor receptacles.

A 20-amp circuit needs at least 12 AWG copper, and 14 AWG copper is limited to a 15-amp breaker (2025 CEC §240.4(D)).

Where receptacles go

  • Walls of living rooms, bedrooms and similar rooms. No point along the floor line of any wall space is more than 6 feet from a receptacle, so on a long wall they are no more than 12 feet apart. A wall space is any wall 2 feet or wider not broken by a doorway or fireplace. Countertop receptacles do not count toward this rule. (2025 CEC §210.52(A))
  • Kitchen countertops. Every counter space 12 inches or wider needs receptacles, so no point along the wall line is more than 24 inches from one, which puts them no more than 4 feet apart. They go on or above the counter, no more than 20 inches above it. (2025 CEC §210.52(C))
  • Islands and peninsulas. Receptacles are not required there, but if none is installed, provisions for adding one later are required. (2025 CEC §210.52(C))
  • Bathrooms. At least one receptacle within 3 feet of the outside edge of each sink, never more than 12 inches below the countertop. (2025 CEC §210.52(D)) No receptacle may be within 3 feet horizontally of a tub or shower, up to 8 feet above the rim or threshold. One exception is a single receptacle for an electronic toilet or bidet seat that is not between the toilet and the tub or shower. (2025 CEC §406.9(C))
  • Outdoors. A one-family house needs at least one outdoor receptacle at the front and one at the back, readily accessible from grade and no more than 6 1/2 feet above it. A deck or porch within 4 inches of the house needs one reachable from it. (2025 CEC §210.52(E))
  • Laundry, garage, hallway. One receptacle in each laundry area; at least one in each garage vehicle bay, no more than 5 1/2 feet above the floor; at least one in a hallway 10 feet or longer. (2025 CEC §210.52)
  • Tamper-resistant. All 15- and 20-amp, 125- and 250-volt nonlocking receptacles in a dwelling, including garages, are listed tamper-resistant, with a few exceptions such as those more than 5 1/2 feet above the floor. (2025 CEC §406.12)

Example: A straight 11-foot counter has no sink or range in it. Each receptacle serves 24 inches on each side, or 4 feet of counter, and 11 ÷ 4 = 2.75, so it needs at least 3 receptacles, for example at 2, 6 and 9 feet from one end. With only two, at 2 and 6 feet, the last 3 feet of counter would be more than 24 inches from a receptacle.

Protecting cable in framing

  • Bored holes and notches in wood. The edge of the hole must be at least 1 1/4 inches from the nearest edge of the stud or joist. If it is closer, or the cable is in a notch, cover it with a steel plate at least 1/16 inch thick, or a thinner listed plate. (2025 CEC §300.4(A))
  • Running along framing. Keep cable at least 1 1/4 inches from the edge where nails or screws are likely, or protect it the same way. (2025 CEC §300.4)
  • Metal studs. NM cable through holes in metal framing needs listed bushings or grommets covering all metal edges, fastened in place before the cable is pulled. (2025 CEC §300.4)

A plastic grommet does not replace the steel plate in a wood stud.

Burial depth

For 0 to 1000 volts, the minimum cover (from the top of the cable or raceway to the top of finished grade) in ordinary yard locations is (2025 CEC Table 300.5(A)):

Wiring method Minimum cover Source
Direct-burial cable 24 inches 2025 CEC Table 300.5(A)
Rigid metal or intermediate metal conduit 6 inches 2025 CEC Table 300.5(A)
Nonmetallic raceway listed for direct burial 18 inches 2025 CEC Table 300.5(A)
Residential circuit, 120 volts or less, GFCI-protected, 20 amps or less 12 inches 2025 CEC Table 300.5(A)
Irrigation and landscape lighting, 30 volts or less 6 inches 2025 CEC Table 300.5(A)

Under streets, roads and parking lots every method needs 24 inches. Under a one- or two-family dwelling's own driveway, it is 18 inches, or 12 inches for the GFCI-protected residential circuit. (2025 CEC Table 300.5(A))

Example: Rigid metal conduit needs only 6 inches of cover under a lawn, 18 inches under the house's own driveway, and 24 inches under a street.

Temporary power on the job site: two codes

Cal/OSHA and the Electrical Code both require GFCIs on temporary receptacles, with different scopes.

Rule Cal/OSHA (8 CCR §2405.4) 2025 CEC §590.6
Receptacles covered 120-volt, single-phase, 15- and 20-amp outlets not part of the permanent wiring and used by employees 125-volt, single-phase, 15-, 20- and 30-amp outlets not part of the permanent wiring and used by personnel
Alternative Assured equipment grounding conductor program (tests at least every 3 months) None for these receptacles; an assured program is allowed only for other outlets, or in industrial establishments with qualified personnel where losing power would be more hazardous
Small portable generator Two-wire, single-phase, 5 kW or less, conductors insulated from the frame: exempt Generators of 15 kW or less: GFCI on 15-, 20- and 30-amp receptacles, no small-generator exemption

(8 CCR §2405.4, 2025 CEC §590.6)

Example: A 3 kW two-wire portable generator with its conductors insulated from the frame meets Cal/OSHA's exemption, so Cal/OSHA's GFCI rule does not apply to it. The Electrical Code still requires GFCI protection on its receptacles. When two rules apply, follow the stricter one.

Traps to watch for

  • GFCI is not only for 120 volts. The dwelling list covers 125-volt through 250-volt receptacles, so the dryer receptacle in the laundry area needs it.
  • GFCI and AFCI lists differ. Bathrooms and garages are GFCI but not AFCI; kitchens and laundry areas are both.
  • 6 feet or 24 inches. Walls use 6 feet along the floor line; countertops use 24 inches along the wall line.
  • The wire limits the breaker. A 20-amp breaker on 14 AWG copper is not allowed.
  • Which generator rule? Read whether the question names Cal/OSHA or the Electrical Code.
  • NEC numbers are CEC numbers. A question that cites "NEC 210.8" means the same section in the California Electrical Code.

How to use this guide

Learn the GFCI and AFCI lists side by side using the table, then the receptacle spacing numbers and the burial table. Then answer the practice questions below this guide. Box fill, NM cable, grounding and service rules are also part of the electrical subtopic in Core Trades; for the jobsite safety side, see our B exam safety notes.

Read the Section 3 study notes: Core Trades

Practice questions

Think of your answer first, then open the explanation.

  1. 1. A new home's laundry area has a 125-volt receptacle for the washer and a 120/240-volt, 30-amp receptacle for the electric dryer. Under the California Electrical Code, which of them need GFCI protection?

    Core Trades

    • A. Only the washer receptacle
    • B. Only the dryer receptacle
    • C. Neither, because laundry areas are not on the GFCI list
    • D. Both receptacles
    Show answer

    Correct answer: D

    • A. Only the washer receptacle

      The rule covers receptacles up to 250 volts, so the dryer receptacle is included too.

    • B. Only the dryer receptacle

      The 125-volt washer receptacle in the laundry area also needs GFCI protection.

    • C. Neither, because laundry areas are not on the GFCI list

      Laundry areas are one of the dwelling locations listed in 210.8(A).

    • D. Both receptacles

      Correct answer

      Correct: both are 250 volts or less on circuits of 150 volts or less to ground.

    Explanation

    California Electrical Code section 210.8(A) requires GFCI protection in dwelling units for all 125-volt through 250-volt receptacles supplied by single-phase branch circuits rated 150 volts or less to ground in the listed locations, and laundry areas are on the list. A 120/240-volt dryer circuit is 120 volts to ground, so the dryer receptacle is covered as well as the washer receptacle.

  2. 2. In a new house, which of these areas is NOT on the California Electrical Code's dwelling-unit list for AFCI protection of 120-volt, 15- and 20-amp branch circuits?

    Core Trades

    • A. Kitchen
    • B. Laundry area
    • C. Bathroom
    • D. Hallway
    Show answer

    Correct answer: C

    • A. Kitchen

      Kitchens are on the dwelling-unit AFCI list.

    • B. Laundry area

      Laundry areas are on the dwelling-unit AFCI list.

    • C. Bathroom

      Correct answer

      Correct: bathrooms are not on the dwelling-unit AFCI list (they are on the dormitory list).

    • D. Hallway

      Hallways are on the dwelling-unit AFCI list.

    Explanation

    California Electrical Code section 210.12(B) requires AFCI protection for 120-volt, single-phase, 10-, 15- and 20-amp branch circuits supplying outlets or devices in dwelling-unit kitchens, family rooms, dining rooms, living rooms, parlors, libraries, dens, bedrooms, sunrooms, recreation rooms, closets, hallways, laundry areas and similar areas. Bathrooms are not on the dwelling-unit list; their receptacles need GFCI protection under 210.8(A).

  3. 3. Receptacles are being laid out along a long, unbroken wall of a new home's living room. Under the California Electrical Code, what is the farthest any point along the floor line of that wall may be from a receptacle?

    Core Trades

    • A. 4 feet
    • B. 6 feet
    • C. 10 feet
    • D. 12 feet
    Show answer

    Correct answer: B

    • A. 4 feet

      4 feet is the most a countertop receptacle spacing can be (24 inches each way), not the wall rule.

    • B. 6 feet

      Correct answer

      Correct: no point along the floor line more than 6 feet from a receptacle.

    • C. 10 feet

      10 feet is the hallway length that triggers a required receptacle.

    • D. 12 feet

      12 feet is the most two receptacles can be apart, not the distance from any point to a receptacle.

    Explanation

    California Electrical Code section 210.52(A)(1) requires receptacles in living rooms, bedrooms and similar dwelling rooms to be placed so that no point measured horizontally along the floor line of any wall space is more than 6 feet from a receptacle. That is why receptacles on a long wall end up no more than 12 feet apart.

  4. 4. A new kitchen has a straight 10-foot countertop along a wall, with no sink or range in it. Under the 2023 NEC as adopted in the California Electrical Code, receptacles must be placed so that no point along the wall line is more than how far from a receptacle?

    Core Trades

    • A. 24 inches
    • B. 36 inches
    • C. 48 inches
    • D. 6 feet
    Show answer

    Correct answer: A

    • A. 24 inches

      Correct answer

      Correct: no point along the wall line more than 24 inches from a receptacle.

    • B. 36 inches

      36 inches is the bathroom rule (a receptacle within 3 feet of each sink), not the countertop spacing.

    • C. 48 inches

      48 inches is how far apart the receptacles can be, not the distance from any point to a receptacle.

    • D. 6 feet

      6 feet is the general wall-space rule measured along the floor line, not the countertop rule.

    Explanation

    California Electrical Code section 210.52(C)(1) requires receptacles at every kitchen countertop or work surface 12 inches or wider, placed so that no point along the wall line is more than 24 inches, measured horizontally, from a receptacle in that space. In practice the receptacles are no more than 4 feet apart.

  5. 5. A new kitchen has an island countertop, and the owner does not want any receptacle on the island. Under the 2023 NEC as adopted in the California Electrical Code, what is required at the island?

    Core Trades

    • A. At least one receptacle anyway; the owner cannot waive it
    • B. A receptacle in the island's end panel, below the countertop
    • C. Nothing; island countertops have no receptacle requirements
    • D. Provisions at the island for adding a receptacle later
    Show answer

    Correct answer: D

    • A. At least one receptacle anyway; the owner cannot waive it

      The 2023 text does not require a receptacle on the island itself.

    • B. A receptacle in the island's end panel, below the countertop

      No receptacle below the countertop is required; the rule calls for future provisions instead.

    • C. Nothing; island countertops have no receptacle requirements

      Not quite: if there is no receptacle, provisions for a future one are required.

    • D. Provisions at the island for adding a receptacle later

      Correct answer

      Correct: with no island receptacle, provisions for a future one must be made.

    Explanation

    California Electrical Code section 210.52(C)(2) does not require receptacles on island or peninsular countertops, but if they are installed they must follow the location rules of 210.52(C)(3). If no receptacle is provided to serve the island or peninsula, provisions must be made at the island or peninsula for adding one in the future.

  6. 6. An electrician bores holes through wood studs for NM cable. At one stud, the edge of the hole ends up 1 inch from the face of the stud. What does the California Electrical Code require there?

    Core Trades

    • A. Nothing, because 1 inch is enough clearance
    • B. Nothing, if the hole is lined with a plastic grommet
    • C. Nothing, if the cable is stapled to the stud within 12 inches of the hole
    • D. A steel plate at least 1/16 inch thick over the cable
    Show answer

    Correct answer: D

    • A. Nothing, because 1 inch is enough clearance

      1 inch is less than the 1 1/4 inches the rule requires.

    • B. Nothing, if the hole is lined with a plastic grommet

      Grommets are required where NM cable passes through metal framing; in wood, a hole this close to the edge needs a steel plate.

    • C. Nothing, if the cable is stapled to the stud within 12 inches of the hole

      Stapling does not protect the cable from nails; the plate is required.

    • D. A steel plate at least 1/16 inch thick over the cable

      Correct answer

      Correct: a 1/16-inch steel plate because the hole is closer than 1 1/4 inches.

    Explanation

    California Electrical Code section 300.4(A)(1) requires the edge of a bored hole in a wood member to be at least 1 1/4 inches from the nearest edge of the member. Where that distance cannot be kept, the cable must be protected from nails and screws by a steel plate or bushing at least 1/16 inch thick, long and wide enough to cover the wiring.

  7. 7. At a house, a 120-volt branch circuit with GFCI protection and a 20-amp breaker feeds a yard light post through direct-burial UF cable. The trench runs under the lawn, not under a driveway. Under Table 300.5(A) of the California Electrical Code, what is the minimum cover?

    Core Trades

    • A. 6 inches
    • B. 24 inches
    • C. 12 inches
    • D. 18 inches
    Show answer

    Correct answer: C

    • A. 6 inches

      6 inches is for RMC or IMC, or for low-voltage irrigation and landscape lighting circuits.

    • B. 24 inches

      24 inches is for direct-burial cable on circuits that do not meet the Column 4 conditions.

    • C. 12 inches

      Correct answer

      Correct: 12 inches for a 120-volt, GFCI-protected residential circuit of 20 amps or less.

    • D. 18 inches

      18 inches is for nonmetallic raceways listed for direct burial, or for dwelling driveways.

    Explanation

    California Electrical Code Table 300.5(A), Column 4, allows 12 inches of cover for residential branch circuits rated 120 volts or less with GFCI protection and overcurrent protection of 20 amps or less, in locations not otherwise listed. A note to the table lets the shallowest depth apply when a Column 1 to 3 wiring method (such as direct-burial cable) is used for a Column 4 circuit. Cover is measured from the top of the cable to the top of finished grade.

    Source

  8. 8. Workers plug tools into the receptacles of a two-wire, single-phase portable generator rated 4 kW. Its circuit conductors are insulated from the frame and all grounded surfaces. Under Cal/OSHA's construction-site GFCI rule (Title 8 section 2405.4), do those receptacles need GFCI protection?

    Core Trades

    • A. Yes, every 120-volt temporary receptacle needs a GFCI
    • B. Yes, unless the generator frame is connected to a ground rod
    • C. No, but only if the cords are tested every 3 months
    • D. No, a generator like this rated 5 kW or less is exempt
    Show answer

    Correct answer: D

    • A. Yes, every 120-volt temporary receptacle needs a GFCI

      Not under section 2405.4, which has an exception for small two-wire generators. (The California Electrical Code's 590.6(A)(3) does require GFCI protection on generators of 15 kW or less; see the explanation.)

    • B. Yes, unless the generator frame is connected to a ground rod

      The exception depends on the generator's size and insulated conductors, not on a ground rod.

    • C. No, but only if the cords are tested every 3 months

      The exception does not depend on the assured grounding program's 3-month tests.

    • D. No, a generator like this rated 5 kW or less is exempt

      Correct answer

      Correct: a two-wire generator of 5 kW or less with insulated conductors is exempt.

    Explanation

    Title 8 section 2405.4(c) requires GFCIs on 120-volt, single-phase, 15- and 20-amp temporary receptacles on construction sites, but receptacles on a two-wire, single-phase portable or vehicle-mounted generator rated not more than 5 kW, with its circuit conductors insulated from the frame and all grounded surfaces, need not have GFCI protection under that section. This 4 kW generator meets the Cal/OSHA exception. The California Electrical Code is stricter: its section 590.6(A)(3) requires listed GFCI protection on all 125-volt and 125/250-volt, single-phase 15-, 20- and 30-amp receptacles that are part of a portable generator rated 15 kW or less, so a generator used for temporary power still needs GFCI-protected receptacles to pass the electrical code.

    Sources

Test yourself