Roof Underlayment and Flashing in California: Slopes, Ice Barriers, Drip Edge and Cool Roofs

Section 3 of 5, about 30% of the B exam

Updated

Under the 2025 California Residential Code (CRC), asphalt shingles need a slope of at least 2:12, with two layers of underlayment from 2:12 up to 4:12 and one layer at 4:12 and steeper (2025 CRC §R905.2.2, §R905.1.1). Where an ice barrier is required, it runs to at least 24 inches inside the exterior wall line (2025 CRC §R905.1.2). Metal flashing is at least 0.019 inch thick (2025 CRC §R903.2.1), sidewall base flashing is at least 4 inches by 4 inches (2025 CRC §R905.2.8.3), and drip edge is required at eaves and rakes (2025 CRC §R905.2.8.5).

This page covers what goes between the roof deck and the roof covering, and how water is kept out at edges, valleys, walls and penetrations. It also lists the minimum slope of each covering, California's Class C fire rule and the Energy Code cool roof numbers. Code rules are in our own words with the 2025 section to look up.

Minimum slope for each roof covering

Slope is rise in inches per 12 inches of run. Each covering has a lowest slope it may go on:

Roof covering Lowest slope Source
Mineral-surfaced roll roofing 1:12 2025 CRC §R905.5.2
Asphalt shingles 2:12 (double underlayment up to 4:12) 2025 CRC §R905.2.2
Clay or concrete tile 2 1/2:12 (double underlayment up to 4:12) 2025 CRC §R905.3.2
Metal shingles, wood shingles, wood shakes 3:12 2025 CRC §R905.4.2, §R905.7.2, §R905.8.2
Slate 4:12 2025 CRC §R905.6.2
Lapped metal panels: no lap sealant / with lap sealant 3:12 / 1/2:12 2025 CRC §R905.10.2
Standing-seam metal, built-up, modified bitumen, single-ply, sprayed foam 1/4:12 2025 CRC §R905.10.2, §R905.9.1, §R905.11.1, §R905.12.1, §R905.13.1
Coal-tar built-up 1/8:12 2025 CRC §R905.9.1

Example: a porch roof framed at 2 1/2:12 can take concrete tile with double underlayment, but not wood shingles or metal shingles (3:12) or slate (4:12).

Underlayment

Under asphalt shingles

Where wind design is not required, the 2025 CRC sets two methods by slope (2025 CRC §R905.1.1):

Slope Underlayment Laps
2:12 up to 4:12 Two layers: a half-width starter strip at the eave, then full-width sheets Each sheet overlaps the one below by half the sheet width plus 2 inches
4:12 and steeper One layer, laid shingle fashion parallel to the eave 2 inches

In both cases end laps are 4 inches, offset 6 feet from course to course. One layer of self-adhering polymer modified bitumen underlayment (ASTM D1970) is an accepted alternative. (2025 CRC §R905.1.1) Areas where wind design is required follow a separate set of underlayment rules in the same section, which this page does not cover.

Worked example: a 3:12 roof gets asphalt shingles. 3:12 is at least 2:12, so shingles are allowed, but it is below 4:12, so it needs the two-layer method.

Under tile

Clay and concrete tile from 2 1/2:12 up to 4:12 also takes double underlayment (2025 CRC §R905.3.2). On slopes of 3:12 and steeper, a 36-inch-wide layer of Type I underlayment runs down the full length of each valley under the valley flashing (2025 CRC §R905.3.9).

Ice barriers

Where there is a history of ice forming along the eaves, an ice barrier is required: at least two layers of underlayment cemented together, or a self-adhering polymer modified bitumen sheet (2025 CRC §R905.1.2).

  • It starts at the lowest edge of every roof surface and runs up to at least 24 inches inside the exterior wall line.
  • On roofs of 8:12 or steeper it must also reach at least 36 inches up the slope from the eave edge.
  • Detached accessory buildings with no conditioned floor area are excepted.

Flashing

Where flashing goes

Flash where a roof meets a wall, wherever the roof changes slope or direction, and around roof openings. A flashing also turns water away where the eave of a sloped roof meets a sidewall. Metal flashing is corrosion resistant and at least 0.019 inch thick (No. 26 galvanized sheet). (2025 CRC §R903.2.1)

Shingle roofs: valleys, sidewalls and drip edge

  • Open valley, metal lining: at least 24 inches wide. (2025 CRC §R905.2.8.2)
  • Open valley, mineral-surfaced roll roofing: two plies, the bottom 18 inches wide and the top at least 36 inches wide. (2025 CRC §R905.2.8.2)
  • Closed valley: one ply of smooth roll roofing at least 36 inches wide, either open-valley lining, or self-adhering polymer modified bitumen underlayment at least 36 inches wide. (2025 CRC §R905.2.8.2)
  • Sidewall (step or continuous) base flashing: at least 4 inches high and 4 inches wide, with the vertical leg running up under any siding. (2025 CRC §R905.2.8.3)
  • Drip edge at both eaves and rakes: pieces overlap at least 2 inches; it extends at least 1/4 inch below the sheathing and at least 2 inches back onto the deck; fasteners at no more than 12 inches on center. (2025 CRC §R905.2.8.5)

The drip edge lap is a favorite question: the underlayment goes over the drip edge at the eave and under the drip edge at the rake (2025 CRC §R905.2.8.5). Water running down the underlayment must land on top of the eave drip edge.

Tile and wood valleys

Covering Valley flashing Source
Clay or concrete tile At least 11 inches each way from the centerline, a splash diverter rib at least 1 inch high, 4-inch end laps, metal at least 0.019 inch 2025 CRC §R905.3.9
Wood shingles No. 26 gage (0.019 inch) metal, 10 inches each way below 12:12, 7 inches each way at 12:12 and steeper, 4-inch end laps 2025 CRC §R905.7.7

Chimneys and other penetrations

  • Cricket or saddle. Required on the ridge side of any chimney or penetration more than 30 inches wide, measured perpendicular to the slope. It is covered with sheet metal or the roof covering. A unit skylight flashed per the maker's instructions needs none. (2025 CRC §R903.2.2)
  • Skylight curb. A unit skylight on a roof sloped less than 3:12 sits on a curb at least 4 inches above the roof, unless the maker's instructions say otherwise. (2025 CRC §R324.6.8)
  • Masonry chimney height. At least 2 feet higher than any part of the building within 10 feet, and at least 3 feet above the highest point where it passes through the roof. (2025 CRC §R1003.9)

Parapets and overflow

Parapet walls get noncombustible, weatherproof coping at least as wide as the wall is thick (2025 CRC §R903.3). Where a parapet would trap water if the roof drains backed up, add overflow drains the same size as the roof drains, or overflow scuppers three times their size with an opening at least 4 inches high, each with its inlet 2 inches above the low point (2025 CRC §R903.4.1).

Roof covering minimums for fire

Outside Fire Hazard Severity Zones and Wildland-Urban Interface areas, a roof covering in California is fire-retardant and at least Class C on every new building; on an existing building when more than 50% of the roof area is replaced within any one-year period; and on any covering used to alter, repair or replace a roof (2025 CRC §R902.1.2). Inside those zones the roof also meets the California Wildland-Urban Interface Code, Title 24 Part 7 (2025 CRC §R902.1.1).

Cool roofs (Title 24, Part 6)

Under the prescriptive rules for single-family homes in the 2025 California Energy Code (2025 Energy Code §150.1(c)11):

Roof Climate Zones Aged solar reflectance Thermal emittance Or SRI
Steep-sloped 10 to 15 0.20 0.75 16
Low-sloped 13 and 15 0.63 0.75 75

Roofs weighing at least 25 pounds per square foot and building-integrated solar panels are excepted. A product used to meet a cool roof rule must be certified and labeled; an uncertified asphalt shingle is given default values of 0.08 reflectance and 0.75 emittance (2025 Energy Code §110.8(i)).

Reroofing in one paragraph

A recover (new covering over the old) is not allowed over a water-soaked or badly deteriorated roof, over slate, clay, cement or asbestos-cement tile, or where the roof already has two or more layers; the roofer tears off to the deck (2025 CRC §R908.4). Rusted or damaged flashings, edgings, outlets and vents are replaced (2025 CRC §R908.5).

Traps and study advice

  • Two slope limits for shingles. 2:12 is the floor; 4:12 is where the second layer of underlayment stops being required.
  • "24 inches inside the wall," not 24 inches from the eave, for the ice barrier.
  • Over at the eave, under at the rake for underlayment and drip edge.
  • 0.019 inch is the metal thickness in almost every flashing rule; "No. 26 gage" is the same thing.
  • Any one year, more than 50% triggers Class C on an existing roof.

Roofer fall protection is in the Safety notes. For the rest of this exam section, read the Core Trades notes.

Read the Section 3 study notes: Core Trades

Practice questions

Think of your answer first, then open the explanation.

  1. 1. What is the minimum roof slope on which asphalt shingles may be installed?

    Core Trades

    • A. 2:12
    • B. 2-1/2:12
    • C. 3:12
    • D. 4:12
    Show answer

    Correct answer: A

    • A. 2:12

      Correct answer

      Correct: R905.2.2 sets 2:12 as the minimum.

    • B. 2-1/2:12

      2-1/2:12 is the minimum for clay and concrete tile (R905.3.2).

    • C. 3:12

      3:12 is the minimum for wood shingles and metal roof shingles.

    • D. 4:12

      4:12 is where single-layer underlayment begins for shingles, and the slate minimum.

    Explanation

    California Residential Code section R905.2.2 allows asphalt shingles only on slopes of 2:12 or greater, with double underlayment required from 2:12 up to 4:12.

  2. 2. Asphalt shingles go on a 3:12 roof in an area where wind design is not required. The roofer is using standard underlayment, not a self-adhering membrane. What underlayment is required?

    Core Trades

    • A. One layer, applied shingle fashion and lapped 2 inches
    • B. One layer, with 4-inch side laps
    • C. Two layers along the first 24 inches above the eave, one layer above
    • D. Two layers: a half-width starter strip, then full sheets lapped half the sheet width plus 2 inches
    Show answer

    Correct answer: D

    • A. One layer, applied shingle fashion and lapped 2 inches

      One layer lapped 2 inches is for slopes of 4:12 or greater.

    • B. One layer, with 4-inch side laps

      One layer is not enough below 4:12.

    • C. Two layers along the first 24 inches above the eave, one layer above

      The double layer covers the whole roof, not just the eave.

    • D. Two layers: a half-width starter strip, then full sheets lapped half the sheet width plus 2 inches

      Correct answer

      Correct: below 4:12, R905.2.2 and R905.1.1 require two layers applied this way.

    Explanation

    California Residential Code section R905.2.2 requires double underlayment for asphalt shingles on slopes from 2:12 up to 4:12, and section R905.1.1 describes it: a half-width strip at the eave, then full-width sheets each overlapping the one below by half the sheet width plus 2 inches.

  3. 3. An ice barrier is required on a dwelling with a 5:12 asphalt shingle roof. From the lowest roof edge, how far must it extend?

    Core Trades

    • A. To 12 inches inside the exterior wall line
    • B. To 24 inches inside the exterior wall line
    • C. To 36 inches inside the exterior wall line
    • D. To 48 inches inside the exterior wall line
    Show answer

    Correct answer: B

    • A. To 12 inches inside the exterior wall line

      Short of the 24-inch minimum.

    • B. To 24 inches inside the exterior wall line

      Correct answer

      Correct: R905.1.2 requires at least 24 inches inside the exterior wall line.

    • C. To 36 inches inside the exterior wall line

      36 inches, measured along the slope from the eave edge, is an added minimum only for roofs of 8:12 or steeper.

    • D. To 48 inches inside the exterior wall line

      More than the code minimum.

    Explanation

    California Residential Code section R905.1.2 says a required ice barrier starts at the lowest edge of every roof surface and continues upslope until it is at least 24 inches inside the building's exterior wall line. Only roofs of 8:12 or steeper add a further minimum of 36 inches measured along the slope from the eave edge.

  4. 4. On an asphalt shingle roof, how is the underlayment lapped with the drip edge?

    Core Trades

    • A. Over the drip edge at the eaves and under the drip edge at the rakes
    • B. Under the drip edge at the eaves and over the drip edge at the rakes
    • C. Under the drip edge at both the eaves and the rakes
    • D. Over the drip edge at both the eaves and the rakes
    Show answer

    Correct answer: A

    • A. Over the drip edge at the eaves and under the drip edge at the rakes

      Correct answer

      Correct: over at the eaves, under at the rakes (R905.2.8.5).

    • B. Under the drip edge at the eaves and over the drip edge at the rakes

      This is reversed.

    • C. Under the drip edge at both the eaves and the rakes

      Wrong at the eaves; underlayment goes over the eave drip edge.

    • D. Over the drip edge at both the eaves and the rakes

      Wrong at the rakes; underlayment goes under the rake drip edge.

    Explanation

    California Residential Code section R905.2.8.5 requires a drip edge at both the eaves and the rakes of a shingle roof. At the eaves the underlayment laps on top of the drip edge; at the rakes the drip edge goes on top of the underlayment.

  5. 5. Step flashing is installed where an asphalt shingle roof meets a sidewall. What are the minimum dimensions of this base flashing?

    Core Trades

    • A. 2 inches high by 4 inches wide
    • B. 3 inches high by 3 inches wide
    • C. 4 inches high by 2 inches wide
    • D. 4 inches high by 4 inches wide
    Show answer

    Correct answer: D

    • A. 2 inches high by 4 inches wide

      Too short; the minimum height is 4 inches.

    • B. 3 inches high by 3 inches wide

      Smaller than the 4-by-4-inch minimum.

    • C. 4 inches high by 2 inches wide

      Too narrow; the minimum width is 4 inches.

    • D. 4 inches high by 4 inches wide

      Correct answer

      Correct: R905.2.8.3 requires at least 4 inches by 4 inches.

    Explanation

    California Residential Code section R905.2.8.3 requires base flashing at a vertical sidewall, continuous or step, at least 4 inches high and 4 inches wide, with the vertical leg running under the siding.

  6. 6. A chimney 36 inches wide, measured perpendicular to the slope, comes through a sloped roof below the ridge. What is required on its ridge side?

    Core Trades

    • A. A cricket or saddle
    • B. A second layer of underlayment only
    • C. A 4-inch curb
    • D. Nothing more than step flashing
    Show answer

    Correct answer: A

    • A. A cricket or saddle

      Correct answer

      Correct: wider than 30 inches, so R903.2.2 requires a cricket or saddle.

    • B. A second layer of underlayment only

      Extra underlayment does not divert water around the chimney.

    • C. A 4-inch curb

      A 4-inch curb is the skylight curb rule for low-slope roofs, not a chimney rule.

    • D. Nothing more than step flashing

      Step flashing alone is not enough on a penetration over 30 inches wide.

    Explanation

    California Residential Code section R903.2.2 calls for a cricket or saddle on the upslope (ridge) side of a chimney or other penetration wider than 30 inches, with the width taken perpendicular to the slope. The cricket is covered with sheet metal or the same material as the roof.

  7. 7. An existing house is outside any Fire Hazard Severity Zone and Wildland-Urban Interface area. When must its entire roof covering be at least Class C?

    Core Trades

    • A. When more than 50 percent of the roof area is replaced within any five-year period
    • B. When more than 25 percent of the roof area is replaced within any one-year period
    • C. Only when the house is sold
    • D. When more than 50 percent of the total roof area is replaced within any one-year period
    Show answer

    Correct answer: D

    • A. When more than 50 percent of the roof area is replaced within any five-year period

      The period is one year, not five.

    • B. When more than 25 percent of the roof area is replaced within any one-year period

      The trigger is more than 50 percent, not 25 percent.

    • C. Only when the house is sold

      A sale is not the trigger in R902.1.2.

    • D. When more than 50 percent of the total roof area is replaced within any one-year period

      Correct answer

      Correct: more than 50 percent within any one-year period (R902.1.2).

    Explanation

    Under California Residential Code section R902.1.2, once more than half of an existing roof's total area is replaced in any one-year period, the whole roof covering must be fire-retardant and at least Class C. Any covering used in a repair, alteration or replacement must also be at least Class C.

    Source

  8. 8. A new single-family home in Climate Zone 12 uses the prescriptive approach. Its steep-sloped roof will be asphalt shingles, and compliance will be shown with reflectance and emittance, not SRI. What minimum aged solar reflectance is required?

    Core Trades

    • A. 0.08
    • B. 0.20
    • C. 0.63
    • D. 0.75
    Show answer

    Correct answer: B

    • A. 0.08

      0.08 is the default value assigned to uncertified asphalt shingles (110.8(i)), which is too low.

    • B. 0.20

      Correct answer

      Correct: 0.20 aged solar reflectance for steep-sloped roofs in Climate Zones 10 to 15.

    • C. 0.63

      0.63 is for low-sloped roofs in Climate Zones 13 and 15.

    • D. 0.75

      0.75 is the minimum thermal emittance, not the reflectance.

    Explanation

    California Energy Code section 150.1(c)11 requires steep-sloped roofs in Climate Zones 10 through 15 to have a minimum aged solar reflectance of 0.20 and a minimum thermal emittance of 0.75 (or an SRI of at least 16).

Test yourself

Try 25 free General Building practice questions from all five sections. Each answer explains the rule and names the code section it comes from. No sign-up.