Under the 2025 California Residential Code (CRC), asphalt shingles need a slope of at least 2:12, with two layers of underlayment from 2:12 up to 4:12 and one layer at 4:12 and steeper (2025 CRC §R905.2.2, §R905.1.1). Where an ice barrier is required, it runs to at least 24 inches inside the exterior wall line (2025 CRC §R905.1.2). Metal flashing is at least 0.019 inch thick (2025 CRC §R903.2.1), sidewall base flashing is at least 4 inches by 4 inches (2025 CRC §R905.2.8.3), and drip edge is required at eaves and rakes (2025 CRC §R905.2.8.5).
This page covers what goes between the roof deck and the roof covering, and how water is kept out at edges, valleys, walls and penetrations. It also lists the minimum slope of each covering, California's Class C fire rule and the Energy Code cool roof numbers. Code rules are in our own words with the 2025 section to look up.
Minimum slope for each roof covering
Slope is rise in inches per 12 inches of run. Each covering has a lowest slope it may go on:
| Roof covering | Lowest slope | Source |
|---|---|---|
| Mineral-surfaced roll roofing | 1:12 | 2025 CRC §R905.5.2 |
| Asphalt shingles | 2:12 (double underlayment up to 4:12) | 2025 CRC §R905.2.2 |
| Clay or concrete tile | 2 1/2:12 (double underlayment up to 4:12) | 2025 CRC §R905.3.2 |
| Metal shingles, wood shingles, wood shakes | 3:12 | 2025 CRC §R905.4.2, §R905.7.2, §R905.8.2 |
| Slate | 4:12 | 2025 CRC §R905.6.2 |
| Lapped metal panels: no lap sealant / with lap sealant | 3:12 / 1/2:12 | 2025 CRC §R905.10.2 |
| Standing-seam metal, built-up, modified bitumen, single-ply, sprayed foam | 1/4:12 | 2025 CRC §R905.10.2, §R905.9.1, §R905.11.1, §R905.12.1, §R905.13.1 |
| Coal-tar built-up | 1/8:12 | 2025 CRC §R905.9.1 |
Example: a porch roof framed at 2 1/2:12 can take concrete tile with double underlayment, but not wood shingles or metal shingles (3:12) or slate (4:12).
Underlayment
Under asphalt shingles
Where wind design is not required, the 2025 CRC sets two methods by slope (2025 CRC §R905.1.1):
| Slope | Underlayment | Laps |
|---|---|---|
| 2:12 up to 4:12 | Two layers: a half-width starter strip at the eave, then full-width sheets | Each sheet overlaps the one below by half the sheet width plus 2 inches |
| 4:12 and steeper | One layer, laid shingle fashion parallel to the eave | 2 inches |
In both cases end laps are 4 inches, offset 6 feet from course to course. One layer of self-adhering polymer modified bitumen underlayment (ASTM D1970) is an accepted alternative. (2025 CRC §R905.1.1) Areas where wind design is required follow a separate set of underlayment rules in the same section, which this page does not cover.
Worked example: a 3:12 roof gets asphalt shingles. 3:12 is at least 2:12, so shingles are allowed, but it is below 4:12, so it needs the two-layer method.
Under tile
Clay and concrete tile from 2 1/2:12 up to 4:12 also takes double underlayment (2025 CRC §R905.3.2). On slopes of 3:12 and steeper, a 36-inch-wide layer of Type I underlayment runs down the full length of each valley under the valley flashing (2025 CRC §R905.3.9).
Ice barriers
Where there is a history of ice forming along the eaves, an ice barrier is required: at least two layers of underlayment cemented together, or a self-adhering polymer modified bitumen sheet (2025 CRC §R905.1.2).
- It starts at the lowest edge of every roof surface and runs up to at least 24 inches inside the exterior wall line.
- On roofs of 8:12 or steeper it must also reach at least 36 inches up the slope from the eave edge.
- Detached accessory buildings with no conditioned floor area are excepted.
Flashing
Where flashing goes
Flash where a roof meets a wall, wherever the roof changes slope or direction, and around roof openings. A flashing also turns water away where the eave of a sloped roof meets a sidewall. Metal flashing is corrosion resistant and at least 0.019 inch thick (No. 26 galvanized sheet). (2025 CRC §R903.2.1)
Shingle roofs: valleys, sidewalls and drip edge
- Open valley, metal lining: at least 24 inches wide. (2025 CRC §R905.2.8.2)
- Open valley, mineral-surfaced roll roofing: two plies, the bottom 18 inches wide and the top at least 36 inches wide. (2025 CRC §R905.2.8.2)
- Closed valley: one ply of smooth roll roofing at least 36 inches wide, either open-valley lining, or self-adhering polymer modified bitumen underlayment at least 36 inches wide. (2025 CRC §R905.2.8.2)
- Sidewall (step or continuous) base flashing: at least 4 inches high and 4 inches wide, with the vertical leg running up under any siding. (2025 CRC §R905.2.8.3)
- Drip edge at both eaves and rakes: pieces overlap at least 2 inches; it extends at least 1/4 inch below the sheathing and at least 2 inches back onto the deck; fasteners at no more than 12 inches on center. (2025 CRC §R905.2.8.5)
The drip edge lap is a favorite question: the underlayment goes over the drip edge at the eave and under the drip edge at the rake (2025 CRC §R905.2.8.5). Water running down the underlayment must land on top of the eave drip edge.
Tile and wood valleys
| Covering | Valley flashing | Source |
|---|---|---|
| Clay or concrete tile | At least 11 inches each way from the centerline, a splash diverter rib at least 1 inch high, 4-inch end laps, metal at least 0.019 inch | 2025 CRC §R905.3.9 |
| Wood shingles | No. 26 gage (0.019 inch) metal, 10 inches each way below 12:12, 7 inches each way at 12:12 and steeper, 4-inch end laps | 2025 CRC §R905.7.7 |
Chimneys and other penetrations
- Cricket or saddle. Required on the ridge side of any chimney or penetration more than 30 inches wide, measured perpendicular to the slope. It is covered with sheet metal or the roof covering. A unit skylight flashed per the maker's instructions needs none. (2025 CRC §R903.2.2)
- Skylight curb. A unit skylight on a roof sloped less than 3:12 sits on a curb at least 4 inches above the roof, unless the maker's instructions say otherwise. (2025 CRC §R324.6.8)
- Masonry chimney height. At least 2 feet higher than any part of the building within 10 feet, and at least 3 feet above the highest point where it passes through the roof. (2025 CRC §R1003.9)
Parapets and overflow
Parapet walls get noncombustible, weatherproof coping at least as wide as the wall is thick (2025 CRC §R903.3). Where a parapet would trap water if the roof drains backed up, add overflow drains the same size as the roof drains, or overflow scuppers three times their size with an opening at least 4 inches high, each with its inlet 2 inches above the low point (2025 CRC §R903.4.1).
Roof covering minimums for fire
Outside Fire Hazard Severity Zones and Wildland-Urban Interface areas, a roof covering in California is fire-retardant and at least Class C on every new building; on an existing building when more than 50% of the roof area is replaced within any one-year period; and on any covering used to alter, repair or replace a roof (2025 CRC §R902.1.2). Inside those zones the roof also meets the California Wildland-Urban Interface Code, Title 24 Part 7 (2025 CRC §R902.1.1).
Cool roofs (Title 24, Part 6)
Under the prescriptive rules for single-family homes in the 2025 California Energy Code (2025 Energy Code §150.1(c)11):
| Roof | Climate Zones | Aged solar reflectance | Thermal emittance | Or SRI |
|---|---|---|---|---|
| Steep-sloped | 10 to 15 | 0.20 | 0.75 | 16 |
| Low-sloped | 13 and 15 | 0.63 | 0.75 | 75 |
Roofs weighing at least 25 pounds per square foot and building-integrated solar panels are excepted. A product used to meet a cool roof rule must be certified and labeled; an uncertified asphalt shingle is given default values of 0.08 reflectance and 0.75 emittance (2025 Energy Code §110.8(i)).
Reroofing in one paragraph
A recover (new covering over the old) is not allowed over a water-soaked or badly deteriorated roof, over slate, clay, cement or asbestos-cement tile, or where the roof already has two or more layers; the roofer tears off to the deck (2025 CRC §R908.4). Rusted or damaged flashings, edgings, outlets and vents are replaced (2025 CRC §R908.5).
Traps and study advice
- Two slope limits for shingles. 2:12 is the floor; 4:12 is where the second layer of underlayment stops being required.
- "24 inches inside the wall," not 24 inches from the eave, for the ice barrier.
- Over at the eave, under at the rake for underlayment and drip edge.
- 0.019 inch is the metal thickness in almost every flashing rule; "No. 26 gage" is the same thing.
- Any one year, more than 50% triggers Class C on an existing roof.
Roofer fall protection is in the Safety notes. For the rest of this exam section, read the Core Trades notes.